X

واحد تولیدات ضدانفجار | داریان

 

EJB113

    • Marking
    • II 2 G Ex d IIB Gb, II 2 D Ex t IIIC Db
    • Certificate No.
    • TUV 11 ATEX 7220 X, TUV 11 ATEX 7090 U
    • Temperature Class
    • T4-T6
    • Ambient temperature
    • –20 °C to +55°C
    • Zones
    • 1, 2, 21, 22
    • Standard
    • EN 60079-0, EN 60079-1, EN 60079-31
    • Rated voltage
    • Up to 690 V
    • Rated current
    • Depends on electrical equipment
    • Ingress Protection
    • IP 66
    • Enclosure material
    • Copper free aluminum alloy
    • Coating
    • Electrostatic polyester coating (optional color)
    • Weight
    • Approx. 58 kg
    • Max. No. of terminals
    • 220x2.5 mm2 in Horizontal Installation / 270x2.5 mm2 in Vertical Installation
    • Terminal cross section
    • Up to 240 mm2
    • External dimension
    • 688x479x304 (LxWxH)
    • Internal Mounting Plate
    • 574x364 mm2 (2mm thickness, hot dipped galvanized)
    • Hinge side
    • Left/Right
    • Bolts and screws
    • Stainless Steel
    • Earth screws
    • M8 stainless steel on inside and out side of body
    • Lid Fixing
    • 20xM10 Stainless Steel bolts
    • Installation Mounting
    • Surface mounted or structure mounted
    • Tread
    • Metric threads ISO261/965 or NPT Threads ANSI B1.20.1
    • L (mm)
    • 688
    • W (mm)
    • 479
    • H (mm)
    • 304
  • Cable entry’s capacity
    • Gland sizes
    • M16
    • M20
    • M25
    • M32
    • M40
    • M50
    • M63
    • Left/Right
    • 45
    • 30
    • 15
    • 14
    • 9
    • 9
    • 5
    • Top/Bottom
    • 30
    • 20
    • 11
    • 10
    • 7
    • 7
    • 3

دسته بندی محصول

جستجوی محصول